Question
At what temperature does the switch send a trap?
Environment
S-Series
Answer
Ambient temperature traps/messages are generated based on the following thresholds (using chassis fan tray temperature sensors):

HOT: 41C or more (then back to WARM at 38C)
WARM: 35C or more (then back to NORMAL at 32C)
NORMAL: 11C – 34C
COOL: 10C or less (then back to NORMAL at 13C)
COLD: 4C or less (then back to COOL at 7C)

Support envTempHot (OID=
1.3.6.1.4.1.52.0.282) and envTempNormal (OID=1.3.6.1.4.1.52.0.284) Cabletron traps/messages based on the following thresholds (using board LM75 temperature sensor):

HOT: 70C or more
NORMAL: 65C or less