VSP9000 System Temp led keeps red after overheating situation

« Go Back

Information

 
TitleVSP9000 System Temp led keeps red after overheating situation
Symptoms
After overheating situation, VSP9K reported temperature alarm and system temperature led changed to red.
Once the air condition was fixed, the temperature led keep in red and VSP9K was generated following alarm:
CP1 HW INFO Module 1, Zones:32C,24C,0C,31C,23C Highest Temp 32C, Lowest Temp 23C, Alarm Threshold 54C Shutdown Threshold 59C
CP1 HW INFO Module 2, Zones:29C,23C,0C,27C,22C Highest Temp 29C, Lowest Temp 22C, Alarm Threshold 54C Shutdown Threshold 59C
CP1 HW INFO Module 3, Zones:26C,25C,35C,33C,42C Highest Temp 42C, Lowest Temp 25C, Alarm Threshold 69C Shutdown Threshold 74C
CP1 HW INFO Module 3, FPGA Temps:52C 52C 55C 54C 53C 55C 51C 51C 48C  Highest Temp:55C, Lowest Temp:48C, Alarm Threshold:90C Shutdown Threshold:95C
CP1 HW INFO Module 3, FA Temps:36C 44C 62C  Highest Temp:62C, Lowest Temp:36C, Alarm Threshold:105C Shutdown Threshold:110C
CP1 HW INFO Module 4, Zones:25C,24C,32C,30C,38C Highest Temp 38C, Lowest Temp 24C, Alarm Threshold 69C Shutdown Threshold 74C
CP1 HW INFO Module 4, FPGA Temps:49C 50C 51C 49C 53C 50C 48C 44C 49C  Highest Temp:53C, Lowest Temp:44C, Alarm Threshold:90C Shutdown Threshold:95C
CP1 HW INFO Module 4, FA Temps:32C 41C 61C  Highest Temp:61C, Lowest Temp:32C, Alarm Threshold:105C Shutdown Threshold:110C
CP1 HW INFO Module 6, Zones:23C,19C,22C,25C,22C Highest Temp 25C, Lowest Temp 19C, Alarm Threshold 59C Shutdown Threshold 64C
CP1 HW INFO Module 8, Zones:23C,19C,21C,24C,21C Highest Temp 24C, Lowest Temp 19C, Alarm Threshold 59C Shutdown Threshold 64C
CP1 HW INFO Module 10, Zones:24C,22C,22C,25C,27C Highest Temp 27C, Lowest Temp 22C, Alarm Threshold 59C Shutdown Threshold 64C
CP1 HW INFO Module 12, Zones:23C,20C,22C,23C,26C Highest Temp 26C, Lowest Temp 20C, Alarm Threshold 59C Shutdown Threshold 64C
CP1 HW INFO Module 1, Zones:33C,24C,0C,31C,23C Highest Temp 33C, Lowest Temp 23C, Alarm Threshold 54C Shutdown Threshold 59C
CP1 HW INFO Module 2, Zones:29C,23C,0C,27C,22C Highest Temp 29C, Lowest Temp 22C, Alarm Threshold 54C Shutdown Threshold 59C
CP1 HW INFO Module 3, Zones:26C,25C,36C,33C,42C Highest Temp 42C, Lowest Temp 25C, Alarm Threshold 69C Shutdown Threshold 74C
CP1 HW INFO Module 3, FPGA Temps:53C 52C 55C 54C 54C 55C 52C 51C 48C  Highest Temp:55C, Lowest Temp:48C, Alarm Threshold:90C Shutdown Threshold:95C
CP1 HW INFO Module 3, FA Temps:36C 45C 63C  Highest Temp:63C, Lowest Temp:36C, Alarm Threshold:105C Shutdown Threshold:110C
CP1 HW INFO Module 4, Zones:25C,24C,32C,30C,38C Highest Temp 38C, Lowest Temp 24C, Alarm Threshold 69C Shutdown Threshold 74C
CP1 HW INFO Module 4, FPGA Temps:49C 51C 51C 49C 53C 50C 48C 45C 49C  Highest Temp:53C, Lowest Temp:45C, Alarm Threshold:90C Shutdown Threshold:95C
CP1 HW INFO Module 4, FA Temps:32C 41C 61C  Highest Temp:61C, Lowest Temp:32C, Alarm Threshold:105C Shutdown Threshold:110C
CP1 HW INFO Module 6, Zones:23C,19C,22C,25C,22C Highest Temp 25C, Lowest Temp 19C, Alarm Threshold 59C Shutdown Threshold 64C
CP1 HW INFO Module 8, Zones:23C,19C,21C,25C,21C Highest Temp 25C, Lowest Temp 19C, Alarm Threshold 59C Shutdown Threshold 64C
CP1 HW INFO Module 10, Zones:24C,21C,22C,25C,27C Highest Temp 27C, Lowest Temp 21C, Alarm Threshold 59C Shutdown Threshold 64C
CP1 HW INFO Module 12, Zones:23C,20C,22C,23C,26C Highest Temp 26C, Lowest Temp 20C, Alarm Threshold 59C Shutdown Threshold 64C

 User-added image
Environment
VSP9000
Cause
Seems like a SW bug which does not clear temperature warning.
Resolution
Cold boot the VSP9K.